Installation andOperationSmart-UPS SUA2200/3000 UXI230 VACTo we rUniterruptible Power SupplySmart-UPS SUA2200/3000 230 VAC UXI Tower User Manual1 Important Safety InformationImportant Safety InformationRead the instructions carefully to become familiar with the equipment before trying to install, operate, service or maintain it. The following special messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not is the safety alert symbol.

Installation and Operation Smart-UPS™ SUA2200/3000 UXI 230 VAC Tower Uniterruptible Power Supply

Tags:

  Operations, Installation, Installation and operation

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of Installation and Operation - - APC USA

1 Installation andOperationSmart-UPS SUA2200/3000 UXI230 VACTo we rUniterruptible Power SupplySmart-UPS SUA2200/3000 230 VAC UXI Tower User Manual1 Important Safety InformationImportant Safety InformationRead the instructions carefully to become familiar with the equipment before trying to install, operate, service or maintain it. The following special messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not is the safety alert symbol.

2 It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or and General InformationInspect the package contents upon receipt. Notify the carrier and dealer if there is any damage. This UPS is for indoor use only. Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive dust or high humidity. Do not operate the UPS near open windows or doors. Be sure the air vents on the UPS are not blocked.

3 Allow adequate space for proper : Allow a minimum of 20 cm clearance on both front and rear sides of the UPS. Environmental factors impact battery life. Elevated ambient temperatures, poor quality utility power, and frequent discharges will shorten battery life. Follow the battery manufacturer recommendations. WARNINGWARNING indicates a potentially hazardous situation which, if not avoided, can result in death or serious injury. CAUTIONCAUTION indicates a potentially hazardous situation which, if not avoided, can result in minor or moderate used to address practices not related to physical injury.

4 The safety alert symbol is not used with this signal SUA2200/3000 230 VAC UXI Tower User ManualIntroductionIntroductionAbout this UPSThe APC by Schneider Electric Smart-UPS is a high performance uninterruptible power supply (UPS). The UPS provides protection for electronic equipment from utility power blackouts, brownouts, sags, surges, small utility power fluctuations and large disturbances. The UPS also provides battery backup power for connected equipment until utility power returns to acceptable levels or the batteries are fully user manual is available on the APC by Schneider Electric web site, contentsRead the Safety Guide before installing the model and serial numbers for all units are located on the rear panel.

5 See the small label with numbers and bar packaging is recyclable; save it for reuse or dispose of it the package contents:Specifications UPS Battery cable assembly IEC jumper cables Input power cord Serial cable USB cable EPO connector Utility connector plug User Manual Safety Guide Warranty CardTemperatureOperating0 C to 40 C (32 F to 104 F)This unit is intended for indoor use only. Select a location sturdy enough to handle the not operate the UPS where there is excessive dust or the temperature or humidity are outside the specified that the air vents on the UPS are not factors impact battery life.

6 High temperatures, poor utility power, and frequent, short duration discharges will shorten battery ElevationOperatingStorage3,000 m (10,000 ft)15,240 m (50,000 ft)Humidity0 to 95% relative humidity, non-condensingWeight36 kg (80 lbs)The model and serial numbers for all units are located on the rear panel. For some models, an additional label is located on the unit chassis behind the front SUA2200/3000 230 VAC UXI Tower User Manual3 InstallationInstallationConnect the BatteriesAn APC by Schneider Electric external battery pack can be used with this unit.

7 Refer to the APC by Schneider Electric Web site , or contact your dealer for information regarding APC by Schneider Electric external battery Party Battery SolutionWhen using a non-APC battery pack, a 48 V battery string should be wired to the UPS using the supplied battery cable A Fuse80 to 140 AFuse48 Volt SystemBattery ConnectorA 140 Amp fuse must be used between the connector cable and the batteries. If parallel strings of batteries are used, each string of four 12 Volt batteries must be provided with an 80 to 140 Amp fuse or fusible link to provide protection in the event of a short SUA2200/3000 230 VAC UXI Tower User ManualInstall PowerChute softwareAccessories (Optional)The UPS is equipped with an accessory SmartSlot.

8 Refer to the APC by Schneider Electric Web site , for available accessories prior to connecting power to the additional computer system security, install PowerChute Business Edition software. This provides automatic, unattended shutdown capabilities on most major network operating systems. Connect Equipment and Power to the UPS1. The UPS features a transient voltage surge-suppression (TVSS) screw located on the rear panel, for connecting the ground lead on surge suppression devices such as telephone and network line : Prior to connecting the grounding cable, ensure that the UPS is NOT connected to utility or battery Connect equipment to the Add optional accessories to the Plug the UPS into a two-pole, three-wire, grounded receptacle only.

9 Avoid using extension utility power cord is supplied in the UPS literature kit. NOTE: Prior to connecting the utility power, connect the ground lead (optional) to the TVSS Turn on all connected equipment. To use the UPS as a master on/off switch. Be sure all connected equipment is switched A runtime calibration is required at initial start-up, when additional batteries are added, old batteries are replaced or if the estimated runtime is found to be inaccurate. Do not use old batteries (two or more years old), and new batteries together.

10 Refer to the Perform a UPS Runtime Calibration section in this manual for calibration PowerChute softwareTo install PCPE, connect the supplied USB cable between the data port on the UPS and to a computer with access to the the computer, go to Select Software Upgrades - PowerChute Personal Edition and the appropriate operating system. Follow directions to download the SUA2200/3000 230 VAC UXI Tower User Manual5 Install PowerChute softwareProgram the UPS for the Number of External BatteriesOption 1: Using PowerChute Business EditionInstall PowerChute software.